News Center
We are dedicated to providing users with cost-effective instruments and meticulous services! Welcome to visit, guide, and negotiate business with us.
Current Position:
Home > News > Industrial News

Vortex Flowmeter Fault Case Analysis: A Quick Guide to Troubleshooting

2025-02-07

Understanding the common faults and troubleshooting methods of vortex flowmeters can help technicians quickly identify and resolve issues, improving efficiency. Below are several fault cases with practical solutions for various vortex flowmeter problems.

Case 1: No Current Output from Vortex Flowmeter

Fault Symptom:
The vortex flowmeter suddenly has no current output.

Troubleshooting:

  1. Check if the power supply is functioning correctly.
  2. Use the handheld device for loop testing. Set different measurement ranges in the parameter settings, but there is still no output.

Solution:

  • Replace the amplifier.
  • Reconfigure essential parameters like K-factor, pipe diameter, and measurement range.
  • After these adjustments, the flowmeter operates normally.

Analysis:
When there is no current output, first check the power supply and perform a loop test. If they are normal, the problem is likely with the amplifier. Replacing the amplifier and resetting the parameters will resolve the issue.

 

Case 2: Flowmeter Displays Flow but There Is No Actual Flow

Fault Symptom:
The system has no flow, but the vortex flowmeter still displays a flow rate.

Troubleshooting:

  1. Check for issues with the small signal cut-off settings.
  2. Inspect the parameter settings—specifically the pipe diameter.

Solution:

  • Correct the pipe diameter in the settings.
  • If the parameters are correct, adjust the low-pass filter capacitor.

Analysis:
This issue is often caused by incorrect parameter settings. By verifying and correcting the pipe diameter or adjusting the low-pass filter capacitor, the flowmeter will display accurate readings.

 

Case 3: Large Measurement Error on Flowmeter Display

Fault Symptom:
The vortex flowmeter shows a significant error in measurements.

Troubleshooting:

  1. Compare the current settings with the technical specifications.
  2. Identify if there is a large deviation between the filter capacitor setting and the fluid's density.

Solution:

  • Adjust the filter capacitor according to the manual.
  • For low-density liquids, use one setting; for low-density gases, use two settings.

Analysis:
Measurement errors are often linked to incorrect filter capacitor settings. Correcting these settings, based on the specifications for the fluid's density, will reduce errors and improve accuracy.

 

Case 4: Flowmeter Displays Zero Flow

Fault Symptom:
The vortex flowmeter displays a reading of zero.

Troubleshooting:

  1. Inspect the coaxial cable for breaks (particularly in split vortex flowmeters).

Solution:

  • Replace the broken coaxial cable.
  • After replacement, the flowmeter will display readings normally.

Analysis:
If the flowmeter shows a zero reading, a damaged coaxial cable is a common cause. Replacing the cable restores the functionality of the flowmeter.

 

Case 5: Unstable Signal Output from Flowmeter

Fault Symptom:
The vortex flowmeter’s signal output is unstable.

Troubleshooting and Solutions:

  1. Verify if the fluid flow exceeds the flowmeter's measurement range.
  2. Check the upstream and downstream pipe sections to ensure proper straight pipe lengths.
  3. Confirm that the fluid is flowing steadily.
  4. Inspect for excessive pipeline vibration, and if necessary, use vibration isolation techniques.
  5. Ensure that there is no strong electromagnetic interference. Improve shielding and grounding if needed.
  6. Check if the sensor is contaminated, damp, damaged, or if wiring connections are loose. Clean or replace the sensor as needed and secure the wiring.
  7. Reassess the sensor installation to ensure proper alignment and sealing.
  8. Adjust the sensor's sensitivity to accommodate different fluid flow conditions.

Analysis:
Unstable signals can result from a variety of factors, such as improper installation, pipeline conditions, or interference. By systematically addressing each possibility, the signal output can be stabilized.
 

These case analyses demonstrate that most vortex flowmeter issues can be quickly identified and resolved with a systematic approach. By carefully checking the power supply, calibration parameters, and physical condition of the components, technicians can restore optimal performance. Proper maintenance and regular checks will reduce the occurrence of these problems, ensuring that your flowmeter operates efficiently.
 

If you want to know more about the flow meter or flow meter selection, please consult the Aister flow meter manufacturer email: sales@aistermeter.com for help.

 

Frequently Asked Questions (FAQ)

Q1: How often should I recalibrate my vortex flowmeter?
It is recommended to recalibrate your vortex flowmeter annually, or more frequently if you notice any inaccuracies or irregularities in the measurements.

Q2: What should I do if the flowmeter output remains unstable after troubleshooting?
If the problem persists, contact the manufacturer’s technical support team for further assistance. There could be an underlying issue that requires professional attention.

Q3: Can external factors like temperature or pressure affect the flowmeter?
Yes, external factors such as temperature, pressure, and even the medium's density can affect the performance of the vortex flowmeter. Always consider these variables during installation and calibration.

Share To:


Get a Quotation
Please fill out the following form to provide more details about your requirements, contacts, and desired products. We will promptly contact you for further confirmation.