Note on the selection of accessories in the selection of vortex flowmeter

In the selection process of the vortex flow meter, in addition to the selection of a high-precision type in a comprehensive consideration of the demand, other accessories of the vortex flow meter are also very important, such as the selection of flow transmitters, the selection of compensatory pressure transmitters, and so on.

Rated 4.9/5 based on 320 customer reviews
Share:
Content

1, measurable media

When measuring medium flow rate, instrument range and aperture measurement of general media, the full degree flow rate of the vortex flowmeter can be selected in the range of measuring medium flow rate 0.5-12m /s, and the range is relatively wide.

The selection of instrument specifications (caliber) is not the same as the process pipeline, it should be determined whether the measured flow range is within the flow rate range, that is, when the pipeline flow rate is low and can not meet the requirements of the flow meter or when the measurement accuracy cannot be guaranteed at this flow rate, it is necessary to reduce the instrument caliber, so as to improve the flow rate in the tube and obtain satisfactory measurement results.

2. Selection of vortex flow transmitter

The VA type piezoelectric vortex flow transmitter is used in the saturated steam measurement. Due to the wide range of the vortex flow meter, in practical applications, the main consideration is that the flow rate of saturated steam measured should not be lower than the lower limit of the vortex flow meter, that is to say, the fluid flow rate must not be less than 5m/s.

According to the size of the amount of steam used, vortex flow transmitters of different calibers can be selected, rather than the existing process pipe calibers.

3, pressure compensation pressure transmitter selection

Since the saturated steam pipeline is long and the pressure fluctuation is large, pressure compensation must be used. Taking into account the corresponding relationship between pressure, temperature and density, only pressure compensation can be used in the measurement. Because the saturated steam pressure of the pipeline is in the range of 0.3-0.7MPa, the measuring range of the pressure transmitter can be selected as 1MPa.